Telaire® 7001 Handheld CO2 Monitor

PIC Electronics - Controller Solutions for the HVAC Industrry

Equipped with Telaire's patented Dual Beam Absorption Infrared™ technology, the Telaire® is an easy-to-use CO2 / temperaure monitor designed for use in residential and commercial applications. With the ability to display CO2 readings in less then 30 seconds, the monitor is an ideal tool for: identifying energy saving opportunities in over-ventilated spaces, determining if air quality complaints are due to insufficient ventilation, or locating the presence of combustion fumes generated from vehicles and appliances. The Telaire® 7001 is also equipped with an output for recording data via an accessory cable and data logger. Recorded data can be graphed and printed using our Windows® based VG Graphing Software.

Specifications

Method Dual Beam Absorption Infrared
CO2 Channel
Measurement Range 0-4,000 ppm voltage output
0-10,000 ppm display
Sensitivity ±1 ppm
Accuracy ±50 ppm or 5% whichever is greater
Repeatability ±20 ppm
Temperature Dependence ±0.1% of reading per ºC or ±2 pmm per ºC, whichever is greater, referenced at 25ºC
Pressure Dependence 0.13% of reading per mm Hg (Corrected via user inputfor elevation)
Annual Drift ±20 ppm typical
Response Time 0-90% < 60 seconds for 90% of step change
Warm-Up Time < 60 seconds @ 22ºC
Operating Conditions 0 - 50ºC (32º - 122ºF)
0-95% RH, non-condensing
Storage Temperature -40 - 60ºC (-40 - 140ºC)
Calibration Interval 12 months, offset adjustment using single gas at 0-1,000 ppm CO2. Full factory calibration available
Temperature Channel
Temperature Range Voltage output - 0 - 40ºC (32 - 104ºF)
Display - 0 - 50ºC (32 - 122ºF)
Display Resolution 0.1ºC (0.1ºF)
Display Options ºC, ºF, or off. Set with panel button
Accuracy ±1ºC (2ºF)
Response Time 20-30 minutes (case must equilibrate with environment)
Calibration Interval
12 months, offset adjustment using temperature standard at 10 - 30ºC (50 - 86ºF)
Full factory calibration available
Output - Analog
CO2 0-4VDC linear, 1mV / ppm (4,000 ppm max)
Temperature 0-4VDC linear, 0 - 40ºC (32 - 104ºF)
Output Impedance 100 Ohms
Wiring Connection Via RJ-45 to DB9 serial data cable
Response Time 20-30 minutes (case must equilibrate with environment)
Display LCD with independent CO2 / temperature readings (panel buttons set elevation, ºC / ºF, calibration functions)
Power Supply
Battery Type Four AA batteries, not included
Battery Opertion 80 hours (alkaline)
External 6VDC from external AC/DC adapter, included
Power Requirements 100mA peak, 20mA average from 6VDC
Certification FCC Class 15 Part B

Downloads

Datasheet
Manual